Aspirating system base unit, maximum range 75m

Aspirating system base unit, maximum range 75m

  • high sensitivity aspirating smoke detection system
  • device to control air flow to adjust the sensitivity
  • 1 x SSD31 on board integrated detector with 0,02 %/m - 10 %/m sensitivity range alarm
  • maximum range in C class: 75m
  • configuration with integrated dipswitch and rotary switch
  • 4 alarm levels / pre-signalling
  • standard panel reporting
  • protection class IP54
  • dimensions W195 x H290 x D140mm
  • ABS-Blend UL 94-V0 grey/anthracite housing
  • weight 1,95 kg
  • operating temperature -10°C/+ 55°C
  • power supply 14-30Vdc, power consumption 80mA max (without RIM36)
  • certified CPR 305/2011, EN54-20, class A, B and C

Code: ASD531 Categories: ,